******Update 12:43 hrs******
This repair is complete and all power systems are again functioning according to design.
******Non-Service Impacting Maintenance******
At 11:00 hrs PST Wednesday, January 27th, 2010 digital.forest will make an emergency repair to one of our UPS systems. This repair should have no noticeable impact to delivered power in the facility.
This repair is necessary to replace a failed capacitor on a static transfer switch that was discovered during a routine inspection by digital.forest staff on Tuesday, February 26th. The capacitor does not provide power to any critical systems but is a part of the transfer switch that isolates the UPS system from the critical load during maintenance. The failure of the capacitor is such that the dielectric (in this case oil) is leaking in small amounts into the static switch. This failure poses no risk of power outage, fire, or short-circuit in any of the digital.forest data center infrastructure. It is our policy to repair any failed component in our critical power infrastructure immediately, so long as the repair does not increase risk of power delivery failure.
The repair will not require wrapping power around the UPS system which would involve transferring power from utility to generator. The vendor engineer will perform the work while the equipment is energized. We estimate that the work will require one hour to complete and will provide an update here once all work is complete.
************
digital.forest remains committed to providing our customers with the highest level of service, the greatest degree of protection, and the most transparent communications. If you have any questions or concerns about the above maintenance, please contact your account manager. Our account management staff is available Monday through Friday from 08:00 hrs PST until 17:00 hrs PST at 877-720-0483 Option 2.
posted by digital.forest at 10:49 PM on Tuesday, January 26, 2010
Categories: Emergency Maintenance